Features
• True Sine Wave Output
• 50 KHz Design
• ZERO Changeover time
• IGBT Based Inverter
• Double Conversion Technology
• Suitable for Indian Conditions
• UPS Monitoring Software Facility with CD and cables supporting popularoperatingsystems
• SinglePCBDesign-SleekinSize -LCDDisplay
|
| |
| Technical Specification |
| Model |
BT1000VA - BT6000VA |
| Rated Power |
1KVA 2KVA 3KVA 6KVA |
| DC Bus |
36V 96V 96V 240V |
| INPUT |
| Phase/Wire |
Single-phase 2 wire + G |
| Voltage |
230V+/-20%
( 220V UPS can start to feed normal when Mains 132V ) |
| Efficiency |
47-53HZ |
| OUTPUT |
| Phase/Wire |
Single-phase 2 wire + G |
| Voltage |
230V+/-1% |
| Waveform |
Sinewave<3% THD |
| Voltage Regulation |
+/-1 .5% |
| LCD Display |
All Status |
| Frequency |
50Hz+/- 0.2% |
| Transient Response |
+/-5% for 1 00% step load. 2ms recovery |
| Overload Capacity |
120% for 25s, 150% for 1s |
| Load Power Factor |
0.8 lagging, Load PF range; 0.7 lagging to 0.8 leading within watt capacity |
| Battery Type |
SMF (Sealed Maintenance Free) battery |
| Min. Back up time (In Minute) |
10-30
(Can be Extended to 8 Hours) |
| Recharging Time |
5 hours up to 90% capacity |
| Efficiency |
86% |
| Accoustic noise |
<45db |
| Protection |
Overload, Short circuit, surge clamping voltage
(470V for 230V UPS) |
| Noise Filter |
Noise rejection capability comply FCC Class B (40 db for 0-100 Khz, 70 db for 100 Khz - 500 Mhz) |
| Indicators/Alarm |
Mains normal, Inverter/Bypass feed, Fault, Load /Battery level indicators. Alarm is initiated for all abnormal status. |
| Computer Interface |
9 - Pin D - type connector for computers |
| Environment |
Temperature Humidity
0-40 degree C upto 95% non condencing |
| Dimension(WxDxH) in mm |
145x400x220 192x460x340 192x460x340 192x460x340 |
| Gross Weight (Kg) |
7.0 15.0 16.0 35.0 |
| |
|